Level Sensing Tips for Process Control
Key points
Level sensing is one of the most common functions for process control but it also uses a wide range of different technologies to achieve the same goal; it is therefore important to select the correct design for each application to ensure a reliable and accurate system.
Greg Wainhouse, Midlands Area Technical Sales and Sensors expert at Bürkert UK, offers an explanation on some of the various designs available.
The top 10 level sensing technologies break down like this:
The first distinction to make is the purpose of the level signal – is it required to provide a point level such as an alarm or a continuous signal for level monitoring?
1. Float
– One of the most common forms of point level detection. Although simple in design the float offers a reliable solution. The actual switching mechanism can either be internal and activated by the movement of the float as the level rises or external where a magnet switches a reed contact as the position of the float is moved by the liquid level.
2. Tuning Fork
– This sensor is set to vibrate at its mechanical resonance frequency and when it becomes submerged in either liquid or solid, the frequency changes. This change is detected and converted into a switching command by the on-board electronics. The discrete sensors discussed so far are often used in conjunction with continuous level detection systems, acting as alarm points for over-filling (high-high) and leak or dry pumping (low-low).
3. Ultrasonic
– The transducers in these devices emit ultrasonic pulses that are reflected off the surface of the liquid – the time taken is proportional to the distance between the sensor and the liquid.
This time is also affected by the temperature of the atmosphere above the media, the soundwave has to travel through and a compensation factor is used by the on-board electronics to derive the precise level within the vessel. In applications involving changing atmospheric gases, foaming liquids or objects in the path of the ultrasonic pulse, reduced reliability and repeatability may be experienced.
4. Radar
– In principle radar operates in a similar way to ultrasonic, but the pulses travel at the speed of light and again; the reliability and repeatability can be affected – but this time by the dielectric constant of the fluid. However, radar can provide very accurate level data and also compensate for fixed structures within the vessel.
The downside can be that the initial cost of the sensor is relatively high, but several manufacturers are making this technology more accessible to the wider market.
5. Guided microwave
– Also known as guided radar, overcomes many of the initial calibration issues associated with conventional radar sensing by using a cable or rod to guide the signal to the fluid surface and back to the transmitter. This design makes it a lot more reliable than through-air radar or ultrasonic, because the guide provides a more focussed signal path.
However, the sensors are limited to the length of cable or rod but with solutions up to 75m there is a wide array of probes to suit many applications.
6. Laser
– This technology is a flexible, easy to set up and cost effective solution for non-contact continuous level detection of bulk solids and opaque fluids. However, being based on light reflection, it is less well suited to clear liquids, dust & vapour contaminated atmospheres and applications affected by foam.
7. Hydrostatics
– Hydrostatic pressure is one the most popular level sensing solutions on the market for liquids. Used in vessels open to atmosphere, they are unaffected by changes in media dielectric, atmospheric dust and vapours.
However, as they are mounted on the base or underside of the vessel and measure head-pressure via a ceramic or thin-film stainless steel element, the reliability of measurement technique for level will be greatly affected if the media density changes.
8. Differential Pressure
– Conventional hydrostatic sensors are confined to applications where the storage vessel is open to atmospheric pressure. For situations where a pressurised tank is in use, it is also necessary to measure the atmospheric pressure above the media using a second sensor.
The two pressure signals are then evaluated to give the actual hydrostatic pressure of the liquid and the corresponding level. However, this arrangement is subject to errors due to changes in density and temperature but these can only be mitigated by additional compensating factors, such as additional sensors.
9. Capacitance
– This relatively common approach can be used with solids, liquids and mixed materials which act as a capacitor. The sensor needs to be calibrated to the specific material to account for varying dielectric constants and differences in vessel design.
More recent developments have produced a contact-free measurement system that has widened its application. However, the accuracy of a capacitance sensor depends on a homogeneous dielectric constant throughout the storage vessel. The reliability of these sensors can also be heavily influenced by media sticking to the sensitive probe.
10. Load cell
– The use of strain gauges provides a non-contact measurement system that is built into the support structure of the storage vessel. However, this means that the design and construction of the vessel must account for the use of load cells in order to deliver accurate level measurements. In addition, changes to product density will also greatly affect the reliability of the measurement in the vessel.
Selecting the most appropriate level sensor requires a number of variables to be considered, especially increasingly stringent regulations requiring more precise and reliable level measurement. Improvements to process control enables product quality to be increased while also reducing costs and waste.
Ultimately, the number of different technologies and the increasing amount of sophisticated electronics available to process engineers can make the selection process quite daunting.
Fortunately, help is at hand from the experienced engineers at Bürkert which have considerable expertise in designing and installing process control systems for a wide variety of applications.
Further information about Bürkert, the wide range of sensors and other fluid control devices can be found by contacting Kirsty Anderson, Marketing Manager by Email: kirsty.anderson@burkert.com , or by phone +44 (0) 1285 648720 or by visiting the website, www.burkert.co.uk.
Burkert Fluid Control Systems
- 01285648720
- sales.uk@burkert.com
- http://www.burkert.com/
- Fluid Control Centre 1 Bridge End Gloucestershire Cirencester GL7 1QY GB
About us
Bürkert is present in thirtyfive countries around the world. We also work with a large network of distributors and partners, which means we are as close as possible to our customers. This global presence ensures full service and support to all of our customers in every country around the world. Research is the lifeblood of our company.
At Bürkert, we are never satisfied with the status quo and are continually seeking new technologies and solutions for our customers. Every year, our people develop new and highly advanced products and solutions, ranging from integrated process measurement and control units to the most sophisticated systems used in pharmaceutical research. To be a market leader, we are also an R&D leader.
Therefore, our investment in research & development is one of the highest in our industry. In our research centres in Germany and France, 150 people are committed to working for a common future for our company and our customers. We are committed to offering our expertise wherever it is needed, anywhere in the world. This global presence ensures that our advances in fluid control technology are also global.
What we do in a nutshell
Manufacture of process equipment. One of the few manufacturers to provide solutions for the complete control loop.
Where we supply to
UK Ireland, Europe
Industries we supply to
Food and Beverage, Pharmaceutical Cosmetics Toiletries, Water and Wastewater
-
Surface Acoustic Wave (SAW) Technology: Advanced Flow Measurement and Biofilm Prevention in WFI Loops
Bürkert, a leader in flow control solutions, has introduced an innovative flowmeter that employs Surface Acoustic Wave (SAW) technology. This...
-
Bürkert Launches Ultra High-pressure Valves For Hydrogen Applications
Liquid and gas flow control specialist Bürkert has launched a range of valves designed to control ultra high-pressure flow for...
-
A Question Of Reliability: Supply And Control Devices For Industrial Printers
In the world of industrial and commercial printing, the efficiency and precision of ink supply and control systems are crucial...
-
UK’s first hydrogen kiln test rig helps manufacturers make a sustainable switch
A hydrogen-fuelled kiln test rig is helping brick and ceramics manufacturers to support the energy transition. In a UK first,...
-
Bürkert’s OALAB simplifies chlorine measurement for industrial carbon filters
Common in pharmaceutical, food and beverage applications, industrial high-rate granular activated carbon (GAC) filters remove chlorine from water supplies, safeguarding...
-
Tradition benefitting from technology: Controlling the brewing process
The food and beverage industry is continually evolving, driven by the need for enhanced efficiency, quality, and safety. Central to...
-
FLOWave | Oil dosing (English)
-
Feldbus Gateway Modul ME43: How to operate FLOWave (DE)