Safety Instrumented Function (SIF) Demand: What Should a Functional Safety Engineer Do Next?

By Jonathan Campion CEng BEng FS Eng (TÜV Rheinland # 6632/13, SIS) MIET

Listen to this article
Jonathan Campion - Safety Instrumented Function (SIF) expert

Introduction: What Happens After a Successful Safety Instrumented Function Demand?

You arrive at the office as usual.  The morning call agenda between management and operations is dominated by an unplanned process trip that’s caused a production outage.  A Safety Instrumented Function (SIF) has successfully responded to a genuine process demand.  The plant is safe, the cause has been identified, and the shutdown system appears to have functioned correctly.

As the Functional Safety Engineer responsible for the SIF, what should you do next?

Most engineers would investigate the initiating event, confirm the shutdown, document the incident and return the plant to service.  However, there are two further questions…

What Should a Functional Safety Engineer Review After a SIF Demand?

First, has the event challenged the initiating event frequency assumed during the original LOPA?

Second, has the successful demand provided new evidence regarding the current Functional Safety Integrity of the SIF itself?

This article explores the second question.

SIL Verification vs Operational Performance: Why Real-World Evidence Matters

A SIL verification case is fundamentally a design-stage prediction based on assumed failure rates, proof-test intervals, proof-test coverage, repair times, common-cause failures and expected demand rate.

Once the plant is operating, assumptions gradually become evidence through proof tests, maintenance, diagnostics, repairs and occasional genuine process demands.

Should today’s understanding of the SIF rely only on the original assumptions, or also reflect the operational evidence accumulated since commissioning?

A Safety Instrumented Function is not necessarily performing under the same conditions throughout its operational life as those assumed during its original design. Changes in operating conditions, maintenance practices, component degradation and actual demand frequency can all influence the assumptions used in the original SIL verification. Reviewing operational evidence therefore provides an opportunity to assess whether the original reliability assumptions continue to reflect actual plant performance.

SIF Operational Verification: Can a Successful Demand Provide Evidence of Performance?

Not every successful demand demonstrates the same thing.  Some events exercise the complete shutdown path while others exercise only part of it.

Operational demands should not automatically be treated as proof tests, but neither should they necessarily be ignored.  They may provide valuable operational verification of the parts of the SIF that were genuinely exercised.

The extent of the evidence depends on which elements of the Safety Instrumented Function were exercised during the demand. For example, an event that activates the sensor, logic solver and final element provides different evidence from one in which only part of the shutdown sequence has been exercised. Any assessment should therefore distinguish between the components that demonstrably performed their required function and those that were not tested by the event.

Understanding PFDavg and Hazardous Event Frequency in Functional Safety

For a low demand 1oo1 safety function, the familiar approximation of average Probability of Failure on Demand is:

formula 1 average probability of failure

Where SIF Demand: What Should A Functional Safety Engineer Do?is the dangerous undetected failure rate and SIF Demand: What Should A Functional Safety Engineer Do? is the proof-test interval.  The expression reflects the accumulation of latent dangerous failures between proof tests.  The hazardous-event frequency can then be approximated as:

formula 2 hazardous event frequency

Where SIF Demand: What Should A Functional Safety Engineer Do? is SIF demand rate, which is usually the product of the initiating event frequency, conditional modifiers and layers of protection.  Jin, Lundteigen and Rausand proposed a demand-aware measure, SIF Demand: What Should A Functional Safety Engineer Do?, defined through the relationship:

SIF Demand: What Should A Functional Safety Engineer Do?

Their work incorporated demand rate directly into a Markov model and showed how a common measure could be used across low and high demand operation.

PFDavg is particularly important when evaluating low-demand Safety Instrumented Functions because it provides an estimate of the average probability that the SIF will fail to perform its required safety action when demanded. It is therefore a key parameter in SIL verification and in assessing whether a safety instrumented system continues to meet its required performance over time.

Demand Utilisation Ratio (DUR): Linking SIF Demand Frequency to Proof Testing

If operational demands provide useful evidence, how often does that evidence occur?

formula 4 demand utilisation ratio

The Demand Utilisation Ratio (DUR) is not proposed as a new SIL metric.  It simply indicates how frequently operational evidence may become available relative to scheduled proof testing.

The demand utilisation continuum
Screenshot

The continuum illustrates how the relative frequency of operational demands changes in relation to scheduled proof testing. It provides a conceptual basis for considering whether the operational history of a SIF could complement conventional reliability assessments.

The Demand Utilisation Ratio provides a way of considering the relationship between the frequency of genuine demands on a SIF and its scheduled proof-test interval. A higher DUR indicates that operational demands occur more frequently relative to scheduled proof testing. However, the ratio should not be interpreted as a direct measure of SIL or as evidence that the SIF has become more reliable. Its purpose is to help frame the discussion around how operational demands might contribute to an understanding of SIF performance.

Modelling SIF Performance Using a Two-State Markov Model

A deliberately simple two-state continuous-time Markov model was developed to investigate the concept.  

Simple markov model

Low-Demand Operation: Recovering the Conventional PFDavg Result

When DUR becomes very small, the model naturally reproduces the conventional low-demand probability of failure.  Nothing unexpected occurs.  The familiar low-demand result emerges automatically.  This demonstrates that the simplified model behaves consistently with established functional safety practice.

How Demand Frequency Influences the Probability of SIF Failure

Conditional probability of failure
Figure 3 – Conditional probability of failure

The probability that an individual demand encounters a latent dangerous failure evolves smoothly as DUR increases.  There is no abrupt transition.

The Relationship Between SIF Demand Rate and Hazardous-Event Frequency

Hazardous event frequency
Figure 4 – Hazardous-event frequency

Initially the hazardous-event frequency increases almost linearly with demand frequency.  At high DUR it approaches the dangerous failure rate itself.  Again, the transition is continuous.

What Does the Model Tell Us About SIF Operational Reliability?

The model does not suggest that frequent demands make a safety function safer.  Instead, it demonstrates something much more subtle.

This reduces the average time that dangerous failures remain hidden.  However, each additional demand is also another opportunity for a hazardous event.  These competing effects evolve continuously.  The mathematics simply quantifies that changing balance.

The important distinction is between the probability of failure when a demand occurs and the overall frequency of hazardous events. These are related but different measures. An increase in operational demand frequency can influence the probability that a latent failure is exposed while simultaneously increasing the number of opportunities for a hazardous event. Understanding both measures is therefore essential when interpreting the model.

A successful SIF demand tells us something about the process and something about the safety function.

The Future of Operational Evidence in Functional Safety Verification

Rather than proposing a new methodology, this article asks whether operational evidence should play a greater role in our understanding of Functional Safety Integrity throughout the operational lifecycle.

Future work could investigate whether operational evidence can be quantified, how different operational demands provide different levels of verification, and whether operational history can contribute to a continually updated understanding of Functional Safety Integrity.

Further research could also consider how operational data is recorded, classified and incorporated into reliability models. In particular, distinguishing between full SIF demands, partial functional responses and events that do not exercise the complete safety function could help establish a more consistent framework for using operational experience in functional safety assessments.

Conclusion: Why Every Successful SIF Demand Matters

A successful SIF demand tells us something about the process and something about the safety function.

Current practice provides established methods for reviewing process risk.  Equivalent methods for incorporating operational evidence into our understanding of Functional Safety Integrity are much less developed.

Operational demands should not automatically be treated as proof tests, but neither should they necessarily be ignored.

Every successful SIF demand leaves behind more than an operational record.

It leaves behind evidence.

Whether future Functional Safety practice should make greater use of that evidence remains an open question.

But if the purpose of Functional Safety is to understand the integrity of our protection systems throughout their operational life, then perhaps operational experience deserves to become part of that understanding.

References


Frequently Asked Questions (FAQs)

What is a Safety Instrumented Function (SIF)?

A Safety Instrumented Function (SIF) is a safety function implemented by a Safety Instrumented System (SIS) to prevent or mitigate a hazardous event by bringing a process to a safe state. It typically comprises sensors, a logic solver and a final control element working together to achieve a specified level of risk reduction.

What happens when a Safety Instrumented Function operates successfully?

When a SIF responds successfully to a genuine process demand, the immediate priority is to investigate the initiating event and confirm that the process has reached a safe state. Engineers should also review which parts of the safety function operated correctly and determine whether the event provides useful evidence about the system’s operational performance.

Does a successful SIF demand count as a proof test?

Not automatically. A successful demand may provide evidence that particular elements of a Safety Instrumented Function have operated correctly. However, a proof test is designed to reveal dangerous undetected failures and must follow an appropriate documented procedure. The extent of any verification credit depends on which components and failure modes were actually exercised.

What is PFDavg in functional safety?

Average Probability of Failure on Demand (PFDavg) is a measure of the probability that a Safety Instrumented Function will fail to perform its required action when demanded. It is particularly important for low-demand safety functions and is used in determining whether a SIF meets its required Safety Integrity Level (SIL).

What is the Demand Utilisation Ratio (DUR)?

The Demand Utilisation Ratio (DUR) is a proposed measure of the relationship between the frequency of genuine demands on a Safety Instrumented Function and its scheduled proof-test interval. It is expressed as DUR = λDE × TPT and provides a way of considering how frequently operational demands occur relative to scheduled testing. It is not a standalone SIL metric.

How does demand frequency affect functional safety performance?

Demand frequency can influence both the probability of encountering a latent dangerous failure and the overall frequency of hazardous events. Understanding this relationship is important when assessing the operational performance of a Safety Instrumented Function and reviewing the assumptions used in its original SIL verification.

What is the difference between SIL verification and operational verification?

SIL verification assesses whether a Safety Instrumented Function meets its required safety integrity target based on design assumptions and reliability calculations. Operational verification considers evidence gathered during actual plant operation including proof tests, maintenance, diagnostics, repairs and genuine demands.

Why is IEC 61511 important for Safety Instrumented Systems?

IEC 61511 provides the functional safety requirements for Safety Instrumented Systems used in the process industries. It covers the specification, design, installation, operation and maintenance of these systems to ensure they can achieve or maintain a safe process state.

Show More

    Would you like further information about this article?

    Add your details below and we'll be in touch ASAP!


    Input this code: captcha

    jonathancampion

    Jonathan Campion is an Instrumentation & Control Engineer and Technical Director at STOLZ Ltd, specialising in Functional Safety, measurement systems, and process control. With over 20 years' experience in the energy, oil & gas, and process industries, he has led and supported projects across the full SIS lifecycle. Jonathan is a TÜV Rheinland Certified Functional Safety Engineer, a Chartered Engineer, and the inventor of a patented gas-lift optimisation control system. His current interests include probabilistic reliability modelling, Markov analysis, and advancing practical methods for demonstrating and verifying Functional Safety throughout the SIS lifecycle. LinkedIn