Smart Manufacturing

Slam Shut Cabinets

Listen to this article

In 2009 National Grid Gas awarded Drallim Industries the contract for the manufacture of Slamshut Cabinets for their countrywide replacement program. The duration of the contract was seven years with a value of three million GBP.

The cabinets, of which there are sixteen variations, in conjunction with Slamshut valves, monitor the gas pressure and rapidly cut the flow of gas when the pressure in the system exceeds the set point and avoids overpressure conditions.

National Grid had a large number of slam-shut control systems operating on twin-stream and triple stream pressure Regulating Installations (PRIs).  Many installations were over 25 years old and required replacement to ensure that safety systems were kept in good order.

A number of different designs were in operation, all of which performed the same function but varied slightly.

In order to achieve the benefits of standardisation National Grid opted for one particular system design as a replacement.

Slamshut control cabinets for gas networks master (3)

The system is an up-graded version of the original Select-a-Stream which was designed in the East Midlands in 1989.

‘Select-a Stream II’ is a system of slam-shut stream selection designed and developed by National Grid and manufactured by Drallim Industries. It has been developed from, but is not identical to, the original ‘Select-a-Stream’ systems that were used within East Midlands Network of National Grid.  This manual describes the principles of operation, commissioning and maintenance of the equipment.

The system consists of a control cabinet for each regulator stream. For each installation one cabinet is designated as the ‘Master’. The control cabinets for the other streams differ slightly from the ‘master’ in their internal pipework and are designated as ‘Slaves’’

Slamshut control cabinets for gas networks master

The principle of operation for a two-stream installation is as follows:

When the station outlet pressure rises, the lead stream slam-shut will close when its set point is reached. If the outlet pressure continues to rise, the slam-shut on the standby stream will then close. If the outlet pressure subsequently falls, the standby stream slam-shut will reopen to maintain gas supplies. If the outlet pressure again rises above the set point (e.g. If the standby stream is faulty), the standby stream slam-shut will again close and will not reopen. If the outlet pressure falls again, the lead stream will now reopen to maintain gas supply. Should the outlet pressure rise above the set point yet again, the lead stream slam-shut will again close and will not reopen.

The principle for three stream operation is exactly the same. The streams will close in ascending order of set point. When all streams are closed, should the outlet pressure fall, the last slam-shut to close will reopen first. Each stream will only re-open once.

It later became apparent that the customer specified 3-way ball valves, although of superior quality, had begun to fail in the field. This occurred at low temperature due to cross port leakage; a well-known Achilles heel of even the best multiport ball valves. This causedng the Slamshut valves to trip and close at the wrong time, a very unwelcome outcome on a mains gas pipeline. Drallim Industries offered an easy retrofit solution utilising their own Rotary Selector Valve (RSV) which has much more reliable cross port sealing in demanding applications. Afterhad passinged low temperature tests at -40oC, a special variant was produced with matching interface dimensions to that of the failed ball valves. This replacement program was approved by National Grid Gas. Drallim was awarded the contract to rectify the issue and modify the built units with a further value of 1.2 million GBP.

slamshutcabft

Since the completion of the projects Drallim Industries have been given a Licence Agreement by National Grid Gas (now known as Cadent) to promote, manufacture and supply Slam Shut Cabinets of this design to other Gas Networks which has proven very successful; and we  continue to service and repair SlamShut units when they are returned to us by Cadent.

Drallim Industries Limited

Tel: +44(0)1424 205156

email@drallim.com

www.drallim.com

Show More

    Would you like further information about this article?

    Add your details below and we'll be in touch ASAP!


    Input this code: captcha

    Phil Black - PII Editor

    I'm the Editor here at Process Industry Informer, where I have worked for the past 17 years. Please feel free to join in with the conversation, or register for our weekly E-newsletter and bi-monthly magazine here: https://www.processindustryinformer.com/magazine-registration. I look forward to hearing from you!
    Back to top button

    Join 25,000 process industry specialists and subscribe to:

    PII has a global network of suppliers ready to help...